X7 Firmware Update Manual

Return to:  Horner Tech Support FAQ

 

This section includes:

Introduction

Resources

How to Check for Current Firmware

Options for Updating Firmware

Download the Firmware

Steps for Updating Firmware

 

 

Introduction

This guide details how to update or change firmware on the Horner OCS Controllers. Updating firmware to the newest version adds new benefits to the controller. Also, changing firmware is necessary when changing communications between CsCAN and CANopen.

 

WARNING: Firmware updates should only be performed when the equipment being controlled by the OCS is in a safe, non-operational state. Communication or hardware failures during the firmware update process can cause the controller to behave erratically resulting in injury or equipment damage. Make sure the functions of the equipment work properly after a firmware update before returning the device to an operational mode.

 

 

Resources

For further information on this controller, please refer to the following documents on the Horner website.

 

Manual Numbers for X7

User Manual

MAN1155

Datasheet

MAN1156

 

 

How to Check for Current Firmware

To check the firmware revision on a controller, open System Menu > View Status.

 

 

 

Options for Updating Firmware

WARNING: Updating firmware will clear the application program, screens, configurations, and register data. If required, make sure to backup program and register data before updating firmware. The controller’s User Manual has instructions for doing backups.

 

Method A: Removable Media Method

The controller firmware is updated by a bootloader, using a microSD card or USB Flash drive (not through the Cscape Firmware Update Wizard).

 

To update or change firmware:

  1. Download desired Firmware set from the Horner APG website. (Verify CsCAN or CANopen communications.)

  2. Save Firmware files to microSD card or USB, these are the removable media devices.

  3. Update the firmware through the controller’s Firmware Update function

 

NOTE: Files from the Horner website come as a .ZIP file which need to be unzipped and placed in the root of the drive for them to function properly.

 

 

Method B: RS232 Serial Connection

Serial firmware updates are done from Cscape software to the controller’s primary serial port, MJ1 in most cases.

 

 

Method C: Mini USB Port

The mini USB port can be used to update firmware in the Micro OCS series. This is quicker than doing so via MJ1.

 

 

Download the Firmware

In North America, visit https://hornerautomation.com. Go to Support > Controller Firmware and download the most recent firmware set with the correct communication protocol and controller.

 

-OR-

 

In Europe, visit http://www.hornerautomation.eu/support/firmware and click the Firmware tab and download the desired firmware. Create an account to enable access to the latest firmware updates.

 

 

Steps for Updating Firmware

  1. Establish communication between Cscape and the controller using a direct serial connection to MJ1 or USB.

  2. Make sure your application is available on your PC or upload the application.

  3. Make sure the machinery connected to the OCS is in a safe state for firmware update.

  4. Start the firmware update by selecting File > Firmware Update Wizard.

  5. The correct product type should be selected, if it is not select the type of controller from the drop-down list.

  6. Press the Start button.

  7. Wait for the firmware update to complete.

  8. If there is a communication failure check the cable, connections and comm. port setting and try again.

  9. Firmware updates typically delete the user applications to ensure compatibility. You will need to reload your application.

  10. Test the operation of the equipment with the new firmware before returning the OCS system to an operation mode.